Guide · Grid history
Winter Storm Uri: the Texas blackout
In February 2021 a week of arctic cold froze power plants and gas supplies across Texas and the South Central US. Grid operators cut power to millions to keep the system from collapsing. This is what the investigations found.
What happened
From 13 February 2021, arctic air spread over Texas and the South Central US for more than a week. Demand for heat soared just as power plants failed. ERCOT, which runs most of the Texas grid, ordered firm load shed that lasted nearly three consecutive days and peaked at 20,000 MW by 7 p.m. on 15 February. With SPP and MISO, 23,418 MW of load was shed: the largest controlled firm load shed in US history, by the federal investigators' account.
More than 4.5 million people in Texas lost power, some for as long as four days while exposed to below-freezing temperatures for over six days. In Power Out Map's record the storm peaked at 4,802,070 customers out at once across the country. Replay it hour by hour.
Minutes from collapse
Early on 15 February, as plants tripped offline, the Texas grid's frequency fell below 59.4 Hz. It stayed there for 4 minutes and 23 seconds before recovering at 1:55 a.m. Generators are set to disconnect after 9 minutes below that level to protect themselves; had that happened, much of the grid could have gone dark at once rather than in controlled rotations.
Why plants failed
The investigation counted 4,124 outages, derates or failures to start at 1,045 generating units with 192,818 MW of capacity. Three quarters came from freezing (44.2%) or fuel problems (31.4%); at the worst, ERCOT averaged 34,000 MW of generation out for more than two days. Federal regulators noted it was the fourth cold-weather event in ten years to jeopardise the grid because generators were not ready for the cold.
The human cost
The Texas Department of State Health Services confirmed 246 storm-related deaths in 77 counties; 161 were from exposure to extreme cold. Others included 22 motor vehicle accidents, 19 deaths from carbon monoxide poisoning, 10 from fires and 9 from falls.
What changed
The investigation's first key recommendation was mandatory cold-weather standards for generators. New freeze-protection standards were filed with FERC in October 2022, and the current version, EOP-012-3, took effect on 1 October 2025. Even so, NERC's 2025–2026 winter assessment still lists ERCOT among the areas at risk of shortfalls in extreme cold, as data centers push demand higher. See this winter's outlook.
Questions
Quick answers
How many people died in the Texas winter storm of 2021?
The Texas Department of State Health Services confirmed 246 storm-related deaths in 77 counties, 161 of them from exposure to extreme cold (final report, December 2021).
How many people lost power in Winter Storm Uri?
More than 4.5 million people in Texas, some for as long as four days in below-freezing temperatures (FERC and NERC). Power Out Map's record shows 4.8 million customers out at once nationwide at the peak, on 16 February 2021.
How close did the Texas grid come to collapse?
Grid frequency fell below 59.4 Hz and stayed there for 4 minutes and 23 seconds; generators protect themselves by tripping after 9 minutes below that level. Had it lasted longer, the grid could have collapsed entirely.
Why did the Texas grid fail in February 2021?
Power plants failed in the cold. FERC and NERC counted 4,124 outages, derates and failures to start at 1,045 generating units; 75% were caused by freezing (44.2%) or fuel problems (31.4%), mostly natural gas.
What changed after Uri?
Federal regulators made generator cold-weather preparation mandatory: new NERC reliability standards for freeze protection were filed in October 2022, and the current version, EOP-012-3, took effect on 1 October 2025.
Sources
Where this comes from
- FERC, NERC and Regional Entity staff, The February 2021 Cold Weather Outages in Texas and the South Central United States (November 2021)
- Texas DSHS, February 2021 Winter Storm-Related Deaths (December 2021)
- FERC, tracking of responses to the February 2021 recommendations (December 2022)
- NERC, 2025–2026 Winter Reliability Assessment
- ERCOT, Energy Emergency Alert overview (2026)
This guide is general information, not medical, legal, financial or electrical advice. In an emergency call 911. Outage figures are Power Out Map's, from Oak Ridge National Laboratory's EAGLE-I record; see the methodology.